Respuesta :
Answer:
Efficiency, E = 98.25%, Voltage regulation, Vr = 99.5%
Explanation:
Given parameters
Apparent power, S = 50 kVA or 50,000 VA
full load power factor, cosā = 0.9
short circuit
short circuit voltage, Vsc = 48 V
short circuit current, Isc = 20.8 A
short circuit power loss (copper loss), Psc= 617 W
open circuit
Open circuit voltage, Voc = 240 V
open circuit current, Ioc = 5.41 A
open circuit power loss (core loss) Poc = 186 W
Efficiency, [tex]E = \frac{Pout}{Pout + Psc + Poc} * 100[/tex]
Pout = Scosā , where S is as defined above
Pout = 50 * 0.9
Pout = 45kW or 45,000W
E = (Pout/(Pout + Psc + Poc)) * 100%
E = (45000/(45000 + 617 + 186)) * 100%
E = 98.25%
Voltage Regulation, Vr = Er cosā + Ex sinā
Er = Isc * Rpu * cosā , where Rpu = per unit resistance
Ex = Isc * Xpu * sinā , where Xpu = per unit reactance
from P = I²R where R = P/I²
Rpu = Rsc = Psc/(Isc)² = 617/(20.8)² = 1.4261 ohms
Zpu = Vsc/Isc = 48/20.8 = 2.3077 ohms
from Z² = R² + X²
X² = Z² - R²
X = ā(Z² - R²)
Xpu = ā((2.3077)² - (1.4261)²)
Xpu = 1.8143 ohms
cos ā = 0.9
ā = arccos 0.9 = 25.84
sin ā = sin 25.84 = 0.44
Isc = 20.8 A
Voltage Regulation, Vr = (20.8 * 1.4261 * 0.9) + (20.8 * 1.8143 * 0.44)
Vr = 99.5 V
Given Information:
Apparent power = S = 50 kVA
Primary voltage = Vp = 2400 V
Secondary voltage = Vs = 240 V
Short circuit current = Isc = 20.8 A
Short circuit voltage = Vsc = 48 V
Short circuit power = Psc = 617 W
Open circuit current = Ioc = 5.41 A
Open circuit voltage = Voc = 240 V
Open circuit power = Poc = 186 W
Power factor = pf = 0.9 leading
Required Information:
Efficiency = Ī· = ?
Voltage regulation = VR = ?
Answer:
Efficiency = 98.24%
Voltage regulation = 0.42%
Explanation:
Efficiency is given by
Ī· = output power/input power
Where output power can be found by
output power = S*pf
output power = 50,000*0.9
output power = 45,000 W
Input power is the sum of output power and losses
input power = output power + Pcu + Pcore
The short circuit test is conducted to find out the copper losses
Pcu = Ā 617 W
The open circuit test is conducted to find out the core losses
Pcore = 186 W
input power = 45,000 + 617 + 186
input power = 45,803 W
Therefore, the efficiency is
Ī· = 45,000/45,803
Ī· = 0.9824
Ī· = 98.24%
Voltage regulation is given by
VR = (Vnl - Vfl)/Vfl * 100%
Where Vnl is the no load voltage and Vfl is the full load voltage
Vfl = 2400 V
The load current is given by
I = 50,000/2400 < cosā»Ā¹(0.90)
I = 20.83 < 25.84° A  (since the pf is leading, the angle is positive)
Vnl = Vfl + I*(Req + jXeq)
Req and Xeq can be determined from short circuit test parameters
Req = Psc/Isc²
Req = 617/20.8²
Req = 1.42 Ī©
Zeq = Vsc/Isc
Zeq = 48/20.8
Zeq = 2.307 Ī©
Xeq = ā(Zeq² - Req²)
Xeq = ā(2.307² - 1.42²)
Xeq = j1.818 Ī©
Vnl = 2400 + (20.83 < 25.84)*(1.42 + j1.818)
Vnl = 2400 + (10.115 + j46.97)
Vnl = 2410.11 + j46.974 V
Vnl = 2410.57 < 1.11° V
VR = (Vnl - Vfl)/Vfl * 100%
VR = (2410.11 - 2400)/2400 * 100%
VR = 0.42 %
A lower value of voltage regulation is desired which signifies that the variation in voltage is low and the voltage at the load is very close to supply voltage.