Generators are mechanical devices that use electromagnetic induction to produce electricity. For a load of 200 MW, P₁ is 80 MW and P₂ is 120 MW.
Load sharing is the sharing and operational functioning of the multiple generators together.
Given,
Total load = 200 MW (P₁ +P₂)
For an economic load dispatch, the minimal conditions should be,
I(C₁) = I(C₂)
0.2 P₁ + 60 = 0.3 P₂ + 40
0.2 P₁ - 0.3 P₂ = -20
From the total load, the individual values are calculated as:
0.2 (200 -P₂) -0.3 P₂ = -20
40 - 0.2 P₂ -0.3 P₂ = -20
60 = 0.5 P₂
P₂ = 120 MW
P₁ + 120 = 200
P₁ = 80 MW
Therefore, P₁ = 80 MW and P₂ = 120 MW.
Learn more about load sharing here:
https://brainly.com/question/14727379
#SPJ4