Incremental cost of two generators ic1 = 0. 2 p1 60, ic2 = 0. 3 p2 40 and the ratings of the generator are 150 and 250 mw. Find the load sharing of each generator for a load of 200 mw?

Respuesta :

Generators are mechanical devices that use electromagnetic induction to produce electricity. For a load of 200 MW, P₁ is 80 MW and P₂ is 120 MW.

What is load sharing?

Load sharing is the sharing and operational functioning of the multiple generators together.

Given,

Total load = 200 MW (P₁ +P₂)

For an economic load dispatch, the minimal conditions should be,

I(C₁) = I(C₂)

0.2 P₁ + 60 = 0.3 P₂ + 40

0.2 P₁ - 0.3 P₂ = -20

From the total load, the individual values are calculated as:

0.2 (200 -P₂) -0.3 P₂ = -20

40 - 0.2 P₂ -0.3 P₂ = -20

60 = 0.5 P₂

P₂ = 120 MW

P₁ + 120 = 200

P₁ = 80 MW

Therefore, P₁ = 80 MW and P₂ = 120 MW.